Omron Load Cell Module NX-RS1201
To get started with omron load cell module NX-RS1201
with Sysmac Studio
. This modules supports 4 wire and 6 wire load cells. Load cell module are simple complex systems with ADC
and amplifier
. Amplifier amplifies and input signal from the load cell and ADC
converts the amplified signal to digital value which can be used for the logic.
Required components​
- NX/NJ Motion Controller
- Load cell Module
NX-RS1201
Add Module​
To add module to the CPU Rack
or Remote IO Rack
, Go to Configuration and Set
in Multiview Explorer
. Expand CPU/Expansion Racks
and Select CPU Rack
.
Select Load Cell Input Device
in Toolbox Group
and Select & Insert NX-RS1201 Ver1.0
.
Wiring​
NX-RS1201
supports both 4
or 6
wire configuration.
4 Wire Connections​
| | SHEALD A1 B1
+--+---+----+ +------+ +-------------+
| (OUT+) |<--|------|----->| SIG+ | S+ |<----+
| | | | |------|------| |
| (OUT-) |<--|------|----->| SIG- | S- |<-+ |
| | | | |------|------| | |
| (IN+) |<--|------|----->| EXC+ | EXC+ |<-|--+
| | | | |------|------+ |
| (IN-) |<--|------|----->| EXC- | EXC- |<-+
| | +---+--+ |------|------|
| | | | NC | NC |
+-----------+ | |------|------|
LOADCELL | | NC | NC |
6-WIRE | |------|------|
+---------| SHLD | SHLD |
|------|------|
+-----| SG | SG |
| +-------------+
| A8 B8
EARTH
In 4 wire config, Signal wires are not provided by the load cell, To avoid module in to thinking, it's not connected to the load cell, S+
, S-
wires should be connected to EXC+
and EXC-
respectively.
S+ -------------- EXC+
S- -------------- EXC-
6 Wire Connections​
(SIG-)
+----------------------------------------------+
| (SIG+) |
| +----------------------------------------+ |
| | SHEALD A1 B1 | |
+--+---+----+ +------+ +-------------+ | |
| (OUT+) |<--|------|----->| SIG+ | S+ |<--+ |
| | | | |------|------| |
| (OUT-) |<--|------|----->| SIG- | S- |<----+
| | | | |------|------|
| (IN+) |<--|------|----->| EXC+ | EXC+ |
| | | | |------|------+
| (IN-) |<--|------|----->| EXC- | EXC- |
| | +---+--+ |------|------|
| | | | NC | NC |
+-----------+ | |------|------|
LOADCELL | | NC | NC |
6-WIRE | |------|------|
+---------| SHLD | SHLD |
|------|------|
+-----| SG | SG |
| +-------------+
| A8 B8
EARTH
Module Configuration​
To edit the configuration of the module, Right click on the module and select Edit unit Operation Settings
.
Required parameters are as bellow
Load cell Rated Capacity​
Rated capacity can be obtained from the datasheet of the load cell and can as to setting. Standard operating rule of thumb is milligrams multiplier
.
Let's assume Rated capacity is 5 KG
. It is 5000 g
and 5000000 mg
. This can be set as Rated Capacity
to measure the weight to smallest denominator milligram if the load cell is rated for it.
Standard Weight​
Standard weight is something we use for SPAN
calibration of the load cell. Let's say given applicated, minimum measuring weight is 10g
. Span
can be calibrated at 10g
for optimum results.
Rated capacity is set at 5000000
which is 5 KG
. So, per gram value would be 1000
and for 10g
value would be 10000
.
Load cell Rated Output​
Load cell module amplifies the received voltage based on the given rated output the connected load cell.
This value can be found on the datasheet of the load cell. IT would be around 2mV/V
on average. If it's not printed on load cell or not found on the datasheet, contact vendor/dealer/manufacturer.
Calibration​
Calibration is divided in to 2 parts.
To perform calibration, right click on the module and select Calibration and Data Trace
. Remove all the obstruction and turn of any fans to avoid false calibration data. Wait for the Stable Status
to turn from OFF
to ON
.
Zero Calibration​
Zero Calibration will set the current output of the load cell to the zero
. It should be done with all the deadload including mounting hardware.
To perform Zero Calibration, Select Execute Zero Calibration
in Calibration
in Calibration and Data Trace
.
Span Calibration​
SPan Calibration will calculate the output value and sets ADC
values based on current wait and Standard Weight
in the Operation Setting
. It should be done after performing Zero Calibration
and with standard weight as the load.
To perform Zero Calibration, Select Execute Span Calibration
in Calibration
in Calibration and Data Trace
.
After executing the span calibration
value from the load cell should be same as standard weight
value.
Sample program​
Below is simple Structured Text
/ST
(IEC-61131
) to measure the weight.
Loadcell_Value := N2_Ch1_Gross_Weight_Value_Force_Measurement_Value_DINT;
Loadcell_Capacity := REAL#5000;
Loadcell_Rated_Capacity := REAL#5000000;
One_Gram_Value := Loadcell_Rated_Cap / Loadcell_Capacity;
Loadcell_Weight :=(DINT_TO_REAL(Loadcell_Value)) / One_Gram_Value ;